Current - ML912 Logger
Current - ML912 Logger Loggers  Chauvin Arnoux  Test and Measuring Instruments Malaysia, Selangor, Kuala Lumpur (KL), Kajang Manufacturer, Supplier, Supply, Supplies | United Integration Technology Sdn Bhd
Download Files
ML912_Logger.PDF (3.53 MB)
Description
 
For network monitoring,the ML912 logger acquires 64 samples per period. Frequency monitoring is performed on a range of ±2 Hz around the network's rated frequency (50 ou 60 Hz). The harmonic measurements are calculated from these 64 samples (available in the DataView® software). This Simple Logger® II model stores the TRMS values up to 8 times per second depending on the storage interval programmed by the user. The TRMS calculations are performed on a single period.
 
Specifications
 
1 to 1,000 AAC
2 ranges: 100 and 1,000 AAC
152mm sensors
Battery-powered
USB link
Compatible with DataView®
Number of measurements: 240,000
Sampling rate: 64 per period
Recording rate from 8 measurements/s to 1 measurement/day