Voltage - L261 Logger
Voltage - L261 Logger Loggers  Chauvin Arnoux  Test and Measuring Instruments Malaysia, Selangor, Kuala Lumpur (KL), Kajang Manufacturer, Supplier, Supply, Supplies | United Integration Technology Sdn Bhd L261 LOGGER
Download Files
L261_Logger.PDF (3.53 MB)
Description
 
Equipped with a built-in storage capacity of 512 kB, the Simple Logger II models can save up to 240,000 measurements. Depending on the application in progress, users can optimize memory management very simply by selecting the storage mode and the sampling rate. The XRM extended recording mode is included on all the models. These complete instruments offer tools for programming alarm setpoints, delayed triggering, triggering according to a threshold or triggering according to a specified range.The LEDs on the front panel show the logger's status and memory occupation at a glance.
 
The L261 logger is ideal for industrial, commercial or residential supervision, monitoring of voltage harmonics, long-term power supply monitoring, etc.
Specifications:
 
1 input channel
Input connection: 2 recessed banana sockets
Range: 0 to 600 VAC/DC
Resolution: 0.1 V
Sampling rate: 64 samples per period
Storage interval: programmable from 125 ms to 1 day
Recording modes: Start/End, FIFO, XRM extended recording mode
Recording duration: 15 min to 8 weeks, programmable with DataView
Memory: 240,000 measurements (512 kB)
Communication: optical USB 2.0
Power supply: 2 x AA 1.5 V batteries
Battery life: 100 hours to more than 45 days
Electrical safety: IEC 61010 300V CAT IV and 600V CAT III